STOCKING DISTRIBUTOR OF ELECTRICAL WIRE AND CABLE
800-522-9975

 

15KV 133% Power Cable

EPR Insulation - PVC Jacket
MV 105 Power (Copper Tape Shield)
Copper Single Conductor Ungrounded

Inv. ID Number
Conductor Size
Insulation Thickness (mils)
Conductor Diameter (in)
Insulation Diameter (in)
Insulation Shield Diameter
Jack Diameter (in)
Approx Lbs/MFT
Minimum Bending Radius
AMPS (Duct)
AMPS (Air)
 
 
 
 
 
 
 
 
 
 
 
 
 
V04-002-01-BK
2 AWG
220
0.266
0.76
0.82
1.00
650
12
165
215
*
V04-1/0-01-BK
1/0 AWG
220
0.341
0.83
0.89
1.07
820
13
215
290
*
V04-2/0-01-BK
2/0 AWG
220
0.376
0.87
0.93
1.11
928
14
245
335
*
 
 
 
 
 
 
 
 
 
 
 
 
V04-3/0-01-BK
3/0 AWG
220
0.423
0.92
0.97
1.15
1067
14
275
385
 
V04-4/0-01-BK
4/0 AWG
220
0.479
0.97
1.03
1.21
1236
15
315
445
*
V04-250-01-BK
250 MCM
220
0.522
1.02
1.09
1.28
1405
16
345
495
 
 
 
 
 
 
 
 
 
 
 
 
 
V04-350-01-BK
350 MCM
220
0.622
1.12
1.19
1.38
1780
17
415
610
*
V04-500-01-BK
500 MCM
220
0.742
1.24
1.31
1.50
2322
18
500
765
*
V04-750-01-BK
750 MCM
220
0.917
1.42
1.50
1.74
3340
21
610
990
*
 
 
 
 
 
 
 
 
 
 
 
 
V04-1000-01-BK
1000 MCM
220
1.071
1.58
1.67
1.91
4225
23
690
1185
*

 

*Stocked Items

Note: The information shown is aproximate and subject to manufacturer tolerances

Note: To Determine correct ampacity by conductor size, please consult the National Electric Code, latest edition